FE Petro Mechanical Leak Detector for Gasoline and Alcohol Blends
- Piston design offers the maximum flow rate possible by deeping flow
restriction through the leak detector at a minimum. Piston has a full
1 5/8" of travel to move the leak detedtion poppet fully out of
the flow path when product is being pumped.
- Piston cylinder has 5.75 cubic inches (94.2cc) of volume to help minimize
nuisance tripping due to thermal contraction. This also reduces the
number of daily line tests during thermal contraction periods and thereby
extends the life of the leak detector.
- Burnished Brass Cylinder Liner has an 8 to 24 micron finish. The piston
rod is polished stainless steel. Both are designed to minimize friction
by providing an extremely smooth surface to reduce wear or the Teflon
seals.
- Merering Pin is constructed of 416 stainless steel to minimize wear
of the critical 3 GPH leak rate orifice.
- 3rd party certified to comply with US EPA requirements 280.41(B) and
280.44(A) for continous monitoring of pressurized piping.
- Capable of detection 3 GPH line leaks at 10PSI
- Once in the open position MLD remains open during product delivery
to pressures as low as 1 psi. Therefore, the MLD will never close when
sevral nozzles are open at the same time.
- 3rd Party certified to comply with US EPA requirements 280.41(B) and
280.44(A) for continous monitoring of pressurized piping.
- UL listed for installation in all 4" FE Petero Pumps and most
competitive makes.
- Compatible with all blends of motor fuels including alcohol blends
from 0 to 100% ethanol of Methanol, 20% MTBE or ETBE with 80% gasoline,
or 17% TAME with 83% gasoline as well as diesel fuels.
- MLD signals a line leak by allowing less thatn 3 GPM (11.4 LPM) restricted
flow rate, at leak sixes of 3 GPH or greater. Leaks of less than 3 GPH
are indicated by the leak detector taking longer thatn 2 to 3 seconds
to open.
- Time required to make a line test is 2 to 3 seconds when no line leaks
exist and air is puged from piping
- Maximum static head on MLD is 12 feet (3.35m) from tank to dispensing
point.
- Minimum height requirement from 2" NPT port to manhole cover
for clearance is 9" (22.9 cm).
STP-MLD
Price: $569.00